Cara konfigurasi Activation Current Overload ATS48








Purpose Untuk memahami cara setting Current overload pada ATS 48

What units are
effected
1. Altistart 48
2. Integrated Keypad

Details This application is divided into several parts

Section Title
1 Parts List
2 Topology Overview
3 Step by step Setup
4 Remark

Section 1; Parts list

Parts List table Items used in the test

Items Part numbers Description
Altistart  ATS48Cxxx  Soft Start



Section 2; Topology Overview



                                                                         





Section 1; Parts liststep by step setup








OIL    = Reaksi softstart saat terjadi current overload
ALA   = alarm
dEF    = starter LOCK dan menampilkan fault OLC.
OFF    = Tidak ada Proteksi
LOC   = Nilai Overload dalam persen dari Arus nominal motor
tOL     = Timer overload time

Untuk cara kerja overload sesuai dengan grafik diatas.
1. saat arus melebihi LOC ( persentase dari arus nominal motor).
2. Timer (tOL) akan mulai menghitung,
3. Jika timer terlewati maka Alarm akan aktif atau fault OLC ( sesuai setting)
4. Timer reset ke nol jika arus motor yang dideteksi turun dibawah nilai LOC -10%. mis
LOC di 100A, maka timer akan reset jika arus kurang dari 90A (100A-10%).


Dari ilustrasi diatas, jika parameter motor kita masukkan, maka ATS akan mulai mendeteksi
overload saat arus motor melebihi 480A (timer 10s mulai counting), jika sebelum 10 detik arus
motor turun dari 432 A (480-10% hysteresis), maka fault OLC tidak muncul sedangkan jika
setelah 10 detik masih diatas 432A maka akan muncul fault OLC.

Section 4; Remark

Note : Pastikan wiring ats48 telah terkoneksi dengan benar.

Cara Setting Basic ATV320
Cara Setting Preset Speed ATV320
Cara Setting Overload ATV320